What RCD protection is required for the Edel hot water cylinder?


Applicable to models: EDL170-520RF, EDL200UK-630RF, EDL270UK-630RF, EDL200UK-630, EDL270UK-630 

 

The Edel electrical requirements are as follows:

To clarify the RCD protection requirements:

 

The Edel requires a Type-A RCD to protect the product.  When using an RCBO, the current overload side of the breaker needs to be a Type-C 16A RCBO with 30mA Type-A RCD protection.

The Edel uses a fixed speed compressor and not an inverter, therefore a Type-B or Type-F RCD is not required for Edel.