Applicable to models: EDL170-520RF, EDL200UK-630RF, EDL270UK-630RF, EDL200UK-630, EDL270UK-630
The Edel electrical requirements are as follows:
To clarify the RCD protection requirements:
The Edel requires a Type-A RCD to protect the product. When using an RCBO, the current overload side of the breaker needs to be a Type-C 16A RCBO with 30mA Type-A RCD protection.
The Edel uses a fixed speed compressor and not an inverter, therefore a Type-B or Type-F RCD is not required for Edel.
Require additional help? Please follow link below
https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321